GENERAL
FREQUENCY: 50HZ (60HZ is available)
VOLTAGE: 380/220V, 400/230V, 415/240V
MODEL: R-YM25
CAPACITY:25KVA/20KW
ENGINE: YANMAR 4TNV98-GGE
ALTERNATOR: STAMFORD/LEROYSOMER/ MECC ALTE
ENGINE
Heavy duty industrial diesel engine manufactures in accordance with B.S.S. 5514, the engine is capable of providing 10% overload for a minimum of 1 hour in any twelve hour period.
ELECTRICAL SYSTEM
12V D.C electrical system, Low Oil pressure and High water temperature shut down
PROTECTION
Low oil pressure, high water temperature and over speed protections
COOLING SYSTEM
50 Degree Tropical Radiator
ENCLOSURE
Mounted within an enclosure and designed to reduce noise level to less than 75DBA at 1 meter in accordance with E.E.C. regulations. The canopy is manufactured from mild steel with full length doors on either side for ease of maintenance. All components used are pre treated against corrosion and finished in polyester coating.
BATTERY
High capacity maintenance free battery & Battery Charger
ALTERNATOR
Construction in accordance with BS5000, VDE0530, NEMAMG1-22, IEC-34, CSA C22-100
REGULATION
Voltage regulation is maintained within the limits of + or - 5% from no load to full load including cold to hot variations at any power factor between 0.8 lagging and
INSULATION
Stator and rotor insulation is class H standard,
SUPPRESSION
Radio and television suppression is provided to comply with B.S.S. 800/1983
BASE FRAME
The complete generating set s mounted as a whole on a heavy duty steel base frame.
Anti-vibration Mounts
The engine and alternator assembly is isolated from the base frame using anti-vibration mounts.
FUEL TANK
8 hour integral fuel tank mounted within the base frame of the generating set complete with contents indicator, filler neck and drain fittings.
GUARDS
The fan, fan drive and battery charging alternator drive are fully guarded for personnel protection. A stone guard protects the radiator core from accidental damage.
CONTROL PANEL
DEEP SEA Control System
CIRCUIT BREAKER
Mounted case circuit breaker is mounted on the machine in a steel enclosure complete with removable gland plates.
Yanmar 25KVA Diesel Generator